AAQL | Body Style | Multipole-multiple actuator type |
ABTD | Mounting Slot Width | 0.164 inches nominal |
ADAQ | Body Length | 5.768 inches minimum and 5.832 inches maximum |
ADAT | Body Width | 2.020 inches minimum and 2.084 inches maximum |
ADAU | Body Height | 3.515 inches minimum and 3.579 inches maximum |
AEBP | Center to Center Distance Between Terminals Parallel to Length | 3.515 inches minimum and 3.579 inches maximum |
AEBQ | Center to Center Distance Between Terminals Parallel to Width | 0.994 inches minimum and 1.058 inches maximum |
AEBY | Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 2.718 inches minimum and 2.782 inches maximum |
AEHA | Distance Between Centerlines of Mounting Facilities Parallel to Body Width | 0.994 inches minimum and 1.058 inches maximum |
AFJN | Fragility Factor | Moderately rugged |
AGAV | End Item Identification | Runway visual range system 400 (RVR400) |
AJEC | Boss Height | 0.187 inches minimum and 0.251 inches maximum |
AKPX | Pole Quantity | 2 |
APNQ | ARC Quenching Method | Magnetic blowout |
AXHR | Mounting Facility Type and Quantity | 4 threaded hole and 4 slot |
BBRG | Storage Type | General purpose warehouse |
CMLP | Thread Quantity per Inch | 32 |
CPLM | Maximum Continuous Load Current Rating per Pole | 15.0 amperes ac all locations |
CPRF | Operating Voltage Type and Rating per Pole in Volts | 250.0 ac all locations |
CPRG | Maximum Interrupting Capacity Current Type and Rating per Pole in Amps | 5000.0 ac all locations |
CPRH | Circuit Protection Type | Overcurrent all locations |
CPRJ | Trip Release Method | Magnetic-hydraulic all locations |
CPRL | Trip Release Characteristic | Time delay all locations |
CPRN | Ultimate Trip Rating of Continuous Current Rating per Pole in Percent | 125.0 all locations |
CPRQ | Reset Method | Manual |
CPRR | Main Contact Tripping Mechanism Type | Trip free |
CPRT | Manual Actuator Type and Quantity | 2 toggle |
CPRW | Actuator Function | Trip-reset |
CPRX | Actuator Position Designation | At each pole |
CPRY | External Actuator Linkage Arrangement | One and two linked |
CPSM | Internal Trip Release Configuration | Series trip all locations |
CQJX | Nominal Thread Size | 0.138 inches |
CQWN | Trip Delay Time in Seconds per Rated Continuous Current | 0.150 minimum at 200 pct and 0.600 maximum at 200 pct all locations |
CQXF | Inclosure Protection Type for Which Designed | Dustproof |
CWJK | Case Material | Plastic |
FREQ | Frequency in Hertz | 60.0 all locations |
THSD | Thread Series Designator | UNC |