5925-01-018-5655 (CF2-G3-15-3, CF2-G3-15A-250VAC-60HZ-TD3) Data

5925-01-018-5655 (5925010185655) NSN Information

PhotoNSNFSCNIINItem NameINC
5925-01-018-5655 Photo
5925-01-018-56555925010185655Circuit Breaker00136

5925-01-018-5655 Features

MRCParameterCharacteristics
AAQLBody StyleMultipole-multiple actuator type
ABTDMounting Slot Width0.164 inches nominal
ADAQBody Length5.768 inches minimum and 5.832 inches maximum
ADATBody Width2.020 inches minimum and 2.084 inches maximum
ADAUBody Height3.515 inches minimum and 3.579 inches maximum
AEBPCenter to Center Distance Between Terminals Parallel to Length3.515 inches minimum and 3.579 inches maximum
AEBQCenter to Center Distance Between Terminals Parallel to Width0.994 inches minimum and 1.058 inches maximum
AEBYDistance Between Centerlines of Mounting Facilities Parallel to Body Length2.718 inches minimum and 2.782 inches maximum
AEHADistance Between Centerlines of Mounting Facilities Parallel to Body Width0.994 inches minimum and 1.058 inches maximum
AFJNFragility FactorModerately rugged
AGAVEnd Item IdentificationRunway visual range system 400 (RVR400)
AJECBoss Height0.187 inches minimum and 0.251 inches maximum
AKPXPole Quantity2
APNQARC Quenching MethodMagnetic blowout
AXHRMounting Facility Type and Quantity4 threaded hole and 4 slot
BBRGStorage TypeGeneral purpose warehouse
CMLPThread Quantity per Inch32
CPLMMaximum Continuous Load Current Rating per Pole15.0 amperes ac all locations
CPRFOperating Voltage Type and Rating per Pole in Volts250.0 ac all locations
CPRGMaximum Interrupting Capacity Current Type and Rating per Pole in Amps5000.0 ac all locations
CPRHCircuit Protection TypeOvercurrent all locations
CPRJTrip Release MethodMagnetic-hydraulic all locations
CPRLTrip Release CharacteristicTime delay all locations
CPRNUltimate Trip Rating of Continuous Current Rating per Pole in Percent125.0 all locations
CPRQReset MethodManual
CPRRMain Contact Tripping Mechanism TypeTrip free
CPRTManual Actuator Type and Quantity2 toggle
CPRWActuator FunctionTrip-reset
CPRXActuator Position DesignationAt each pole
CPRYExternal Actuator Linkage ArrangementOne and two linked
CPSMInternal Trip Release ConfigurationSeries trip all locations
CQJXNominal Thread Size0.138 inches
CQWNTrip Delay Time in Seconds per Rated Continuous Current0.150 minimum at 200 pct and 0.600 maximum at 200 pct all locations
CQXFInclosure Protection Type for Which DesignedDustproof
CWJKCase MaterialPlastic
FREQFrequency in Hertz60.0 all locations
THSDThread Series DesignatorUNC
TTQYTerminal Type and Quantity4 screw

5925-01-018-5655 Manufacturing Part Numbers (SKUs)

MFG SKUCAGESTATUSISCRNVCRNCCSADCDACHCCRNAAC
CF2-G3-15-308125A23 ZZ
CF2-G3-15-374193H95 TX
CF2-G3-15A-250VAC-60HZ-TD374193H95 TX

5925-01-018-5655 Manufacturer

MFG SKUCAGEManufacturerTypeStatusRole
CF2-G3-15-374193Eaton Corp.AH
CF2-G3-15A-250VAC-60HZ-TD374193Eaton Corp.AH
CF2-G3-15-308125U S Dept of TransportationAA

5925-01-018-5655 FLIS Identification

PMICADPE CODECRITL CODEDEMIL CODEDEMIL INTGNIIN ASGMTESDHMICENACSCHEDULE_BINC
UNA129-MAR-1976P853620004000136

5925-01-018-5655 FLIS Management

MOEREC REP CODEMGMT CTLUSCPHRASE CODEPHRASE STATEMENT
GE-------I

5925-01-018-5655 Demilitarization Codes & Management

DMLPMICHMICADPECCriticalityESDC
APN

5925-01-018-5655 Miscellaneous Management

MOE (S_A)SOSAACQUPUISLCCIICRCMCCSVC
GEG69G1EA0U-------I

5925-01-018-5655 Non-consumable Item Support

MOE RULENIMSCDSOR
B481

5925-01-018-5655 Freight

NMFCNMFC SUBUFCHMCLTLLCLWCCTCCSHCADCACCASHNMF DESC